@ARTICLE{Liu_Jiongde_Harmonic_2020, author={Liu, Jiongde and Chen, Xiaoqiang and Wang, Ying and Chen, Tao}, volume={vol. 69}, number={No 4}, journal={Archives of Electrical Engineering}, pages={891-905}, howpublished={online}, year={2020}, publisher={Polish Academy of Sciences}, abstract={To improve the power quality of a multi-pulse rectifier, a zigzag 18-pulse uncontrolled rectifier with an auxiliary circuit at the DC side is proposed. When the grid-side currents are sinusoidal waves, the required DC side injection currents to be compensated can be obtained by analyzing the AC-DC side relationship of diode bridge rectifiers. Then the 6 compensation currents generated by an active auxiliary circuit are injected into the DC side to eliminate the grid-side harmonics of the rectifier. The simulation results verifying the correctness of the theoretical analysis show that the proposed rectifier can mitigate the harmonic content, as the total harmonic distortion of the grid-side current is about 1.45%. In addition, the single-phase inverter used in the active auxiliary circuit has the characters of simple circuit structure and easy controllability.}, type={Article}, title={Harmonic mitigation in 18-pulse rectifier based on zigzag autotransformer by DC side auxiliary circuit}, URL={http://czasopisma.pan.pl/Content/117670/PDF/art11.pdf}, doi={10.24425/aee.2020.134637}, keywords={18-pulse rectifier, harmonic suppressing, zigzag autotransformer}, }